Aller au contenu principal

Gude EPC PDU SNMP

Contenu du Pack de supervision​

Objets supervisés​

Le Pack Gude Export Power Control collecte les données pour:

  • Power-channels
  • Sp-power-channels

Règles de découvertes​

Nom de la règleDescription
HW-Pdu-Gude-Epc-SNMP-Sp-Power-Channel-NameDécouvre les ports unitaires et supervise leur utilisation

Métriques collectées​

Metric nameDescriptionUnit
pdu.power_channels.active.countNumber of power channels
statusStatus of the channel
ovp statusStatus of the built-in overvoltage protection
ps statusStatus of the power supply
power_channel_name#pdu.interface.power_channel.current.ampereActual CurrentA
power_channel_name#pdu.interface.power_channel.energy.active.kilowatthourAbsolute active energykWh
power_channel_name#pdu.interface.power_channel.frequency.hertzFrequencyHz
power_channel_name#pdu.interface.power_channel.phase.angle.degreePhase angle between voltage and L line current
power_channel_name#pdu.interface.power_channel.active.wattActive powerW
power_channel_name#pdu.interface.power_channel.power.apparent.voltampereL line mean apparent powerVA
power_channel_name#pdu.interface.power_channel.power.factor.countPower factor of channel
power_channel_name#pdu.interface.power_channel.power.reactive.voltampereL line mean reactive powerVar
power_channel_name#pdu.interface.power_channel.voltage.voltActual voltageV

Prérequis​

Afin de contrôler votre Gude Export Power Control, le SNMP doit être configuré.

Installation​

  1. Installer le Plugin sur tous les Collecteurs Centreon :
yum install centreon-plugin-Hardware-Pdu-Gude-Epc-Snmp
  1. Sur l'interface Web de Centreon, installer le Pack Gude EPC SNMP depuis la page Configuration > Gestionnaire de connecteurs de supervision

Configuration​

  • Ajoutez un nouvel Hôte depuis la page Configuration > Hôtes
  • Complétez les champs Adresse IP/DNS, Communauté SNMP et Version SNMP
  • Appliquez le Modèle d'Hôte HW-Pdu-Gude-Epc-SNMP-custom

Si vous utilisez SNMP en version 3, vous devez configurer les paramètres spécifiques associés via la macro SNMPEXTRAOPTIONS. Plus d'informations dans la section Troubleshooting SNMP.

MandatoryNameDescription
SNMPEXTRAOPTIONSExtra options SNMP

Comment puis-je tester le Plugin et que signifient les options des commandes ?​

Une fois le Plugin installé, vous pouvez tester celui-ci directement en ligne de commande depuis un collecteur Centreon en vous connectant avec l'utilisateur centreon-engine :

/usr/lib/centreon/plugins/centreon_pdu_gude_epc_snmp.pl \
--plugin=hardware::pdu::gude::epc::snmp::plugin \
--mode=power-channels \
--hostname=10.30.2.114 \
--snmp-version='2c' \
--snmp-community='gude_ro' \
--verbose

La commande devrait retourner un message de sortie de la forme ci-dessous:

OK: 2 active power channel(s) - All power channel interfaces are ok | 'pdu.power_channels.active.count'=2;;;0; 'Meter-A#pdu.interface.power_channel.current.ampere'=2.45A;;;0; 'Meter-A#pdu.interface.power_channel.energy.active.kilowatthour'=16784.21kWh;;;0; 'Meter-A#pdu.interface.power_channel.frequency.hertz'=50.00Hz;;;0; 'Meter-A#pdu.interface.power_channel.phase.angle.degree'=-189.00;;;0; 'Meter-A#pdu.interface.power_channel.active.watt'=523.00W;;;; 'Meter-A#pdu.interface.power_channel.power.apparent.voltampere'=558.00VA;;;; 'Meter-A#pdu.interface.power_channel.power.factor.count'=0.94;;;0; 'Meter-A#pdu.interface.power_channel.power.reactive.voltampere'=-193.00Var;;;; 'Meter-A#pdu.interface.power_channel.voltage.volt'=228.00V;;;0; 'Meter-B#pdu.interface.power_channel.current.ampere'=0.78A;;;0; 'Meter-B#pdu.interface.power_channel.energy.active.kilowatthour'=7993.61kWh;;;0; 'Meter-B#pdu.interface.power_channel.frequency.hertz'=50.00Hz;;;0; 'Meter-B#pdu.interface.power_channel.phase.angle.degree'=-254.00;;;0; 'Meter-B#pdu.interface.power_channel.active.watt'=151.00W;;;; 'Meter-B#pdu.interface.power_channel.power.apparent.voltampere'=178.00VA;;;; 'Meter-B#pdu.interface.power_channel.power.factor.count'=0.85;;;0; 'Meter-B#pdu.interface.power_channel.power.reactive.voltampere'=-91.00Var;;;; 'Meter-B#pdu.interface.power_channel.voltage.volt'=228.00V;;;0;
Power channel interface 'Meter-A' status: valid, ovp status: ok, power supply status: up, current: 2.45 A, absolute energy active: 16784.21 kWh, frequency: 50.00 Hz, phase angle: -189.00°, active power: 523.00 W, apparent power: 558.00 VA, power factor: 0.94, reactive power: -193.00 Var, voltage: 228.00 V
Power channel interface 'Meter-B' status: valid, ovp status: ok, power supply status: up, current: 0.78 A, absolute energy active: 7993.61 kWh, frequency: 50.00 Hz, phase angle: -254.00°, active power: 151.00 W, apparent power: 178.00 VA, power factor: 0.85, reactive power: -91.00 Var, voltage: 228.00 V

Cette commande contrôle l'utilisation des power channels Gude (--mode=power-channels) ayant pour adresse 10.30.2.114 (--hostname=10.30.2.114) en version 2c du protocol SNMP (--snmp-version='2c') et avec la communauté gude_ro (--snmp-community='gude_ro').

Pour chaque mode, la liste de toutes les métriques, seuils associés et options complémentaires peuvent être affichées en ajoutant le paramètre --help à la commande:

/usr/lib/centreon/plugins/centreon_pdu_gude_epc_snmp.pl \
--plugin=hardware::pdu::gude::epc::snmp::plugin \
--mode=power-channels \
--help

Diagnostique​